Piller Product History Uniblock - T
PLEASE NOTE:
NEW DATA AVAILABLE
- THIS PAGE IS FOR HISTORIC INFORMATION ONLY
TRIBLOCK NOW KNOWN AS UNIBLOCK-T
"Uniblock"
is the parent name for Piller Rotary UPS product. It can be configured in a number of different
ways to suit the application. The Uniblock-T is a new name for the TRIBLOCK.
The Uniblock range:
1) Battery backed Uniblock-S (UBS):
a) Standard module Uniblock-R (UBR):
Redundant module
b) UBSD & UBRD are both of the above systems direct diesel-coupled.
2)
Battery-Less:
a) Uniblock-T (UBT): with Powerbridge
b) UBTD is the UBT systems direct diesel-coupled.
c) UBTDE is the UBTD with the diesel engine rated for the emergency power requirements ie: UBTDE500/500
means 500KVA UPS Power, 500KVA Emergency power, the diesel engine is rated at 1000KVA.
PILLER Premium Power Systems
UNIBLOCK-T Uninterruptible Power Supply with kinetic energy store -
Key components
The main components of the UNIBLOCK-T System are:
A synchronous machine with combined motor and generator windings (Uniblock)
A coupling choke (Piller MagicChoke)
A kinetic energy store linked to the synchronous generator by a thyristor converter
(PowerBridge)
The electrical connection to the mains and to the load is by electro
mechanical switches not power electronics. A by-pass switch circumvents the system for servicing purposes.
The Piller UNIBLOCK machine
The UNIBLOCK synchronous motor/generator
combination is a patented development of a brushless synchronous motor and generator in a single housing
successful in well over 5000 mission-critical high power installations.
The UNIBLOCK machine absorbs current harmonics and reactive currents independent of the load current
and load power factor.
Frequency fluctuations are balanced during independent diesel operation.
Modules up to 1670 kVA available. Parallel operation of modules increases total rated power up to 40 MVA.
The system corrects -20% input under-voltage permanently without diesel support.
Pure sinusoidal output voltage generated by the Piller synchronous motor/generator combination
guarantees highest load voltage quality.
The Piller MagicChoke
The coupling choke used in the UNIBLOCK-T provides the electrical connection to the mains and to the
synchronous motor/generator.
The precisely balanced coupling ("magic choke") compensates
for all disturbances on the mains and so prevents their occurring on the load side.
Harmonic load currents and the reactive power requirement for the load are not transferred to the
mains but delivered by the UNIBLOCK machine.
The special design of the choke ensures a broad input
voltage range and limits reverse currents to the mains during short circuits to less than twice the
rated current.
The Piller POWERBRIDGE
POWERBRIDGE is a high
performance kinetic energy store for bridging short-term supply interruptions. It can store up to
16.5 MWs of energy. Total power failures of up to two minutes may be bridged (depending on load).
This allows sufficient time for diesel units to start up during longer power cuts.
This avoids frequent quick starts which pollute the environment and cause material fatigue.
In addition, POWERBRIDGE overcomes the disadvantages of battery operated systems such as:
costly maintenance
unpredictable battery performance or ageing
temperature dependency

Click here to see this diagram enlarged
. . . MagicChoke
Coupling choke couples load and mains and totally eliminates all disturbances in either direction,
it is the "MagicChoke.'
Kinetic energy store (POWERBRIDGE)
Synchronous Motor/Generator
combination (UNIBLOCK machine)
Click here to see this diagram enlarged
UNIBLOCK-T Voltage Restorer
Acts as a bi-directional filter and provides high quality power
ADVANTAGES
Correction of mains disturbances
Correction of load disturbances
Power factor correction
Extremely high short circuit current
Operation without energy store
Compensation of -20% undervoltage for unlimited time (-100% / 20ms)
UNIBLOCK-T POWERBRIDGE / Battery
Contains the advantages of the UNIBLOCK-T Voltage Restorer,
buffers mains interruptions up to minutes, using kinetic energy store or battery
ADDITIONAL ADVANTAGES
Injects and absorbs high energy instantaneously
Stabilization of frequency (in island application)
Overrides total mains failures for seconds (POWERBRIDGE) or even minutes (Battery)
Compensates undervoltage of -20% continuously without exhausting the energy store