UPCS SPECIFICATIONS

Model

UPCS 100

UPCS 400

Supply

Nominal Voltage

3ph 400/230V + 10% - 15%

3ph 400/230V + 10% - 15%

Nominal frequency

50 Hz + 5%

50 Hz + 5%

Compensation 

Nominal power

100 kVAR

400kVAR

Nominal current

145 A

580 A

Peak current

435 A

1740 A

Max. overload

150% 30 sec.

150% 30 sec.

Analysed harmonics

1 to 60

1 to 60

Harmonic distortion

< 3%

< 3%

Power factor compensation

up to cos phi 0,98 (load dependent)

up to cos phi 0,98 (load dependent)

Regulation Time

instantaneous regulation of voltage(current optional)

instantaneous regulation of voltage(current optional)

General Data

Environment

0o C to 40o C

0o C to 40o C

Losses

5 kW

11 kW

RFI protection

acc. VDE 0875 Level B (N)

acc. VDE 0875 Level B (N)

Air flow requirement

1700 m3/h

3400 m3/h

Dimensions (h x w x d)

1400 x 750 x 800 mm

1900 x 1640 x 860 mm

Weight

1520 kg

2600 kg

Colour

RAL 7035

RAL 7035

Noise

< 62 bB(A)

< 68 dB(A)

Degree of protection

IP20

IP20

Piller reserves the right to make changes to technical data.