APOSTAR AR3 - Specifications:

Type

AR3-10

AR3-15

AR3-20

AR3-30

AR3-40

AR3-60

Output

Rated power (kVA / kW)

10 / 8

15 / 12

20 / 16

30 / 24

40 / 32

60 / 48

Rated current (A)

14

22

29

43

58

87

Autonomy

custom designed

Output voltage

400 V/AC

Voltage tolerance

Static

<+1 %

Dynamic

<+5 % (100 % load step)

Distortion factor

< 3 %

Crest factor

> 3

Output frequency

50 Hz + 1 %…2 % adjustable, mains synchronised

Overload capacity

150 % for 60 sec., 125 % for 10 min.

Input

Input voltage

400 V/AC + 20 %

Input frequency

50 Hz + 10 %

Input current (max.) (A)

18

28

37

55

72

108

Recom. line fuse (A)

20

32

50

63

80

125

General data

Efficiency %

90

90

91

91

92

92

Dimensions (mm)

Width

555

555

555

555

555

800

Depth

720

720

720

720

720

720

Height

1400

1400

1400

1400

1400

1400

Weight (without battery) (kg)

210

220

240

282

330

450

Ambient temperature

0… + 40oC

Noise (dB(A))

48…54

48…54

53…60

53…60

53…60

53…62

Rel. humidity

max. 95 %, non-condensing

RFI

EN 50091-2 " A"

Protection

IP20

Paint finish

RAL 7035

Communication-interfaces

 

RS-232 interface

 

Potential-free contacts for:

 

Mains failure

 

UPS bypassed

 

Battery under-voltage

Options

 

Additional battery modules for extension of autonomy.

 

Batteries with 5 or 10 years service life.

 

External maintenance bypass for complete isolation of the UPS

 

APONET Power Management Software for Auto-Shut-Down.

 

"SNMP adapter" for network integration.

 

Parallel operation for increased power.


Piller reserves the right to make changes to technical data.
Last Updated on 19/12/00 by PTC